Two engineers with the same sample, the same table and the same calipers will still disagree about creepage, because creepage is not a gap. It is the length of the shortest path along an insulating surface between two conductive parts. Measuring it means putting the calipers down and following a line with a rule, around every rib, into every slot, and back out again.
Clearance and creepage are two different measurements
Clearance is the shortest distance through air. It is what a caliper measures, and it is unaffected by the shape of the surface between the two points. Creepage is the shortest distance along that surface, and it is affected by everything: a 1 mm slot adds 2 mm to the path, a 1 mm rib adds 2 mm as well, and a recess adds its depth twice.
The two limits exist for different reasons. Clearance protects against a transient overvoltage jumping the gap, so it depends on the expected impulse level and on altitude. Creepage protects against tracking along a contaminated surface, so it depends on the pollution degree and on the comparative tracking index of the material. A design can satisfy one and fail the other, and it usually does at the point where the designer measured a gap and called it creepage.
| Feature between the two points | Effect on clearance | Effect on creepage |
| Plain surface, no feature | Equal to the gap | Equal to the gap |
| Slot narrower than 1 mm | Increases by the slot depth | Bridges the slot: adds nothing |
| Slot 1 mm or wider | Increases by the slot depth | Adds depth twice (down and up) |
| Rib narrower than 1 mm | Increases by the rib height | Bridges the rib: adds nothing |
| Rib 1 mm or wider | Increases by the rib height | Adds height twice |
| Recess with an undercut | Unchanged | Adds the undercut twice |
Why a narrow slot does not count
The rule that features narrower than about 1 mm are bridged exists because contamination and moisture fill them. A 0.5 mm slot looks like a barrier on a drawing and behaves like a continuous surface in service, so the standard treats it as one. This is the single most common measurement error in a first-pass check, and it always errs on the optimistic side.
The practical consequence: when you widen a 0.6 mm slot to 1.2 mm, creepage improves by twice the depth even though nothing visible changed. When a moulding tool wears and a 1.2 mm slot closes to 0.9 mm, creepage silently drops by the same amount. Tool maintenance is an insulation issue, which is not obvious from the maintenance schedule.
Measuring it in practice
- Mark the two conductive points first. The path is only defined once the endpoints are.
- Use a thin flexible rule or a piece of solder wire bent to follow the surface, then straighten and measure it.
- Follow the surface into every feature wider than 1 mm; bridge every feature narrower.
- Take the shortest path, not the most convenient one. A longer path around a rib does not count if a shorter one exists.
- Record the path in a sketch with the feature widths written on it; a bare number cannot be checked later.
The dimension that is usually forgotten
Creepage is measured between conductive parts, not between terminals. A screw head, a solder blob, a stranded wire end that protrudes 2 mm past the terminal, all are conductive parts. A path measured to the terminal body and not to the wire end can be short by 2 to 4 mm, which is often the entire margin.
The same applies at the other end: a metal enclosure, a fixing screw that touches a metal insert, a shielding can. Each is a conductive part, and each can shorten the path without appearing anywhere in the insulation drawing.
Where the table and the part disagree
Tables in IEC 60664-1 give creepage as a function of pollution degree, material group and working voltage. Reading them backwards, from a required distance to an allowable voltage, is how most designs are checked. The trap is that the table assumes the material group is known, and the material group comes from a tracking test that is often run on a coupon of the same resin but a different colour or a different filler content. Two grades of the same polyamide can sit in different material groups, and the table entry changes by 20 %.
When the data sheet does not state a CTI value with the test method, treat the material as the weaker group and design to that. It costs a millimetre now and saves a redesign later.
Standards referenced: IEC 60664-1 (insulation co-ordination, creepage and clearance tables), IEC 60884-1 clause 29 (clearances, creepage distances and solid insulation for accessories), IEC 60112 (comparative tracking index).